Hello everyone.
I'm using libmodbus.org on a project and found that the RS485 ports on
the TS-7800 are wired in such a way that everything you write to the
port gets echoed to the receive buffer so the library fails because it
takes the sent frame as the response frame :s
I have modified libmodbus to circumvent this problem and want to share
the code with you. You can grab it at:
https://github.com/jaimealsilva/libmodbus
I've also submitted the changes upstream, they're waiting for approval.
You can find more details about the solved problem there:
https://github.com/stephane/libmodbus/pull/35
Any comments will be appreciated.
Thanks.
--